Q. What is the difference between the F4-08THM and the F4-08THM-n?
A. See here.
Q. I connected a thermocouple to the F4-08THM but the temperature reading
is way off or it reads burnout, what's wrong?
A. Make sure that the thermcouple type that you are using matches the
type selected with jumpers on the F4-08THM.
Q.Can I field calibrate my F4-08THM?
A. There are no field adjustments for this module but you can use ladder
logic to add or subtract a calibration factor.
Q. How can I verify the module is functioning correctly?
A. Thermocouple calibrator. Install the calibrate enable jumper before
testing with a thermocouple calibrator. Not all thermocouple calibrators
will function with our module. To detect thermocouple burnout, we send
balanced currents down each leg of the thermocouple wire, most thermocouple
calibrators CANNOT handle this current pulse. We use an NIST traceable
thermocouple calibrator - ALTEK Model 422. Be sure to place the calibrate
enable jumper on a singl post after testing with a thermocouple calibrator.
Q. How much error will thermocouple extension wire introduce?
A. Thermocouple extension wire has a limit of error from 1.7°C to 2.2°C
depending on the type wire. This error can be removed by subtracting
the error from your reading in ladder logic.
|