F4-08MPI (8 Channel Magnetic Pulse Input)
|
| Download User Manual | |||
|
|
| Download Cut Sheet | |||
|
|
|||
| FAQ: | |||
| Q. I'm not getting any input counts when I connect my input to the MPI module. A1 Verify the MPI module's slot dependent V-locations are set up according to the manual. A2 Using a scope, verify the input waveform is a zero-crossing signal. The MPI was designed for a hall effect type sensor with an output of +/-10mV to +/-10V. TTL levels will NOT work. A3 In the module Mode Word V-location force a value of 100H. This will put the module in "raw" counts mode. Any valid pulse will increment the input V-location. Q. I can see raw counts coming in but, the flow rate calculation is not working. A1 You must have a valid K factor entered and you must also make sure that the digits to the right of the decimal point in the K factor is set properly. |
|||