Q. What is the difference between the F3-08TRS-1,-2, and -5?
A. All three part numbers are 8 Point Isolated Relay Output Modules
but each has different current ratings and relay configurations.
F3-08TRS-1 - 10A/Point, 2 Form C relays, 6 Form A relays
F3-08TRS-2 - 5A/Point, 2 Form C relays, 6 Form A relays, User replaceable
fuses
F3-08TRS-5 - 5A/Point, 2 Form C relays, 6 Form A relays, Class I
Division II
Q. Can I switch low voltage and low current signals through these
relays?
A. If the relays have never switched high voltage or inductive loads
then they can be used to switch loads as small as 10mA, otherwise
a wiping current of 100mA minimum is required.
|