F2-08AD-2 (8 Channel Voltage Input)
 
arrow   Link to User's Manual
   
 DL205 Analog I/O User's Manual
 
arrow   Download Chapter from User's Manual
   
DL205 Analog I/O User's Manual
 
arrow   Download Cut Sheet
   
.pdf F2-08AD-2
 
arrow   FAQ:
   

Q. I have programmed the multiplexing logic into my 240/250 but the data is never changing and the channel ID bits are not changing. What's wrong?
A. Most likely the pointer data for the slot your analog module is in is not zeroed. If your F2-08AD-2 is in Slot 0 make sure V7660 and V7670 contain zeros, then power cycle the PLC.